2.7.27 AUTO/MANUAL SWITCH 1

The Auto/Manual Switch 1 (AMS 1) module provides a continuous output signal that is derived
from one of three sources which are the output track value (OTV), control output auto value (CO),
or the manual push button value. The output priority is OTV, CO, and output push buttons. The in-
put variable parameter values also affect the output, as determined by the output selection made.
The two tables that follow list the input variables and the parameters. As shown in the third table,
two logical output signals, L129 and L131, indicate which source is supplying the continuous out-
put signal at C138. An illustration of the AMS 1 module follows the tables.

Inputs

Inputs

WIRELIST

SYMBOL

DATA

TYPE

ASSIGNED VALUE

WIRELIST

SYMBOL

DATA

TYPE

ASSIGNED VALUE

B197

AE1

L

B199

OTV1

C

B198

SWOVT1

L

B200

CO1

C

Output Datapoints: C138, L129, L131

Parameters

Parameters

SYMBOL

DATAPOINT

ASSIGNED VALUE

SYMBOL

DATAPOINT

ASSIGNED VALUE

SWA1

L136

HML1

L146

OTE1

L143

OH1

C145

T3-1

C154

OL1

C146

L131

L129

C138 OUTPUT

0

0

Output push button value.

1

0

Control Output auto value - CO (when SWA = 1 and AE = 1, AUT is true - lower toggle to 1). CO out.

0

1

Output Track Value - OTV (when SWOVT = 0, and OTE = 1, OVTS is true - upper toggle to 1). OTV
out.

1

1

Output Track Value - OTV (same as above, but both toggles at 1).

AE1...auto enable
A/M1...auto/manual
AUT1...auto status
CO1...control output
HML1...hard manual limit
OH1...output high limit
OL1...output low limit
OTE1...output track enable
OTV1...output track value
OUT1...output
OVTS1...output track status
SWA1...auto switch
SWOVT1...output tracking
switch
T3-1...output slew rate

Section 2. FCS Modules

AMS-1

2-39