beautypg.com

5 executing an fcs wirelist, 6 module types, 7 fcs module descriptions – Micromod Micro-DCI: 53MC5000 Multi-Loop Process Controller FLEXIBLE CONTROL STRATEGIES User Manual

Page 14

background image

2.5 EXECUTING AN FCS WIRELIST

The procedure to execute the FCS wirelist is provided in the table that follows:

Executing an FCS Wirelist

STEP

PROCEDURE

1 Enter a 0 into datapoint B000 to stop FCS execution. The MicroMod logo appears on the display screen.

Outputs will no longer be updated but remain at their current values.

2

Load all of the wirelist values and associated module parameters from the worksheet into the PCS using any of
the methods described in the 53MC5000 PCS Instruction Bulletin (e.g., faceplate push buttons, hand held
configurer, MC5FIG module in 53HC3300, etc.).

3

Configure, as applicable, the PCS System Module (e.g., Display List), Communications Module, External I/O
Table, Trend Module, and Totalizer Module. All of these modules are described in the 53MC5000 PCS
Instruction Bulletin. If these modules were already configured, then step 1 of this procedure did not destroy
their contents.

4

Enter a 1 into datapoint B000 to start executing the FCS wirelist program.

2.6 MODULE TYPES

There are 41 FCS module blocks maximum (four loop controller) which can be catagorized into 15
distinct module types. The 15 module types are listed in the table that follows:

Module Types

ITEM

TYPE

NAME(S)

NUMBER OF

FCS MODULE

BLOCKS

1

Status Display 1 LoaderModule

SDT1

1

2

Contact Closure Input Loader Module

CCI0-17

1

3

Analog Input Loader Module

ANI0-8

1

4

Extended Math Module

EMATH A & B

2

5

Math Module

MATH A-F

6

6

Logic Module

LOGIC A-H

8

7

Parameter Load Modules

PLOAD A-E

5

8

Setpoint Generator Modules

SPG 0-3

4

9

Deviation/Alarm Calculation Modules

D/C 0 & 1

2

10

Proportional Inegral Derivative Modules

PID 0 & 1

2

11

Auto/Manual Switch Modules

AMS 0-3

4

12

Control Modules

CON 2 & 3

2

13

Analog Output Loader Modules

ANO 0-4

1

14

Contact Closure Output Loader Modules

CCO 0-5

1

15

Status Display 0 Loader Module

SDT0

1

2.7 FCS MODULE DESCRIPTIONS

The FCS modules are described in the sections that follow in the same order as they appear in Fig-
ures 2-1, 2-2, and 2-3. Each module section has a description, an inputs table, a function code ta-
ble (where applicable), a table of standard parameter datapoints associated with the module
(where applicable), and an illustration of the module.

Section 2. FCS Modules

3-1TXT

2–7