beautypg.com

Start-up, Safety instructions, Specifying the standard settings – Burkert Type 8791 User Manual

Page 54: Running the automatic adjustment x.tune

background image

54

Start-up

14.

sTarT-up

14.1. safety instructions

Warning!

risk of injury from improper operation!

Improper operation may result in injuries as well as damage to the device and the area around it.

• Before start-up, ensure that the operating personnel are familiar with and completely understand the contents

of the operating instructions.

• Observe the safety instructions and intended use.

• Only adequately trained personnel may operate the equipment/the device.

14.2. specifying the standard settings

The basic settings of the positioner are implemented at the factory.

To adjust the positioner to local conditions, the

X.TUNE function must be run following installation.

14.2.1. running the automatic adjustment X.TUNE:

Warning!

Danger due to the valve position changing when the X.TUNE function is running!

When the

X.TUNE is running under operating pressure, there is an acute risk of injury.

• Never run

X.TUNE while a process is running!

• Take appropriate measures to prevent the equipment from being accidentally actuated!

noTE!

avoid maladjustment of the controller due to an incorrect supply pressure or applied operating medium
pressure!

• Run

X.TUNE whenever the supply pressure (= pneumatic auxiliary energy) is available during subsequent

operation.

• Run the

X.TUNE function preferably without operating medium pressure to exclude interference caused by

flow forces.

To run

X.TUNE, the positioner must be in the AUTOMATIC operating status

(DIP switch 4 = OFF).

english

Type 8791