Burkert Type 8791 User Manual

Page 25

background image

25

Technical Data

8.7.

safety positions after failure of the electrical or
pneumatic auxiliary power

The safety position depends on the fluid connection of the actuator to the working connections A1 or A2.

actuator system

Designation

safety positions after failure of the

electrical auxiliary power

pneumatic

auxiliary power

up

down

single-acting

Control function

A

down

Connection according to “Figure 6”

down

up

Connection according to “Figure 7”

up

down

single-acting

control function

B

up

Connection according to “Figure 6”

up

down

Connection according to “Figure 7”

up

down

lower

chamber

upper

chamber

double-acting

Control function

I

Fluid connection see “Figure 8”

not defined

up = lower chamber of the actuator to A2

down = upper chamber of the actuator to A2

Table 4:

Safety Positions

fluid connection: Description for “Table 4”

single-acting actuators
Control function A and B

Double-acting actuators

Control function I

Connection:
working connection A1 to actuator

A2 sealing

Connection:
working connection A2 to actuator

A1 sealing

Connection:
Working connection A1 and A2
to actuator

Safety position:
up = lower chamber to A2
down = upper chamber to A2

Figure 6:

Connection A1

Figure 7:

Connection A2

Figure 8:

Connection with CFI

english

Type 8791