beautypg.com

Functions, Basic functions – Burkert Type 8791 User Manual

Page 32

background image

32

Functions

10.

funcTiOns

The positioner type 8791 has different basic and additional functions which can be configured and parameterized
via the DIP switches or the communications software.

10.1. Basic functions

The following basic functions can be activated via the DIP switches (

CUTOFF and CHARACT) or changed

(

DIR.CMD).

function

Description

Dip switches Off

On

DIR.CMD

Effective sense of direction
between input signal and set-point
position

1

Ascending

Descending

CUTOFF

Sealing function for position
controller

2

Sealing function off

Sealing function on

CHARACT

Selection of the transfer charac-
teristic between input signal and
stroke (correction characteristic)

3

Linear characteristic Correction

characteristic

Table 14:

Basic functions of DIP switches

The following basic function can be changed via the communications software only.

function

Description

factory settings

INPUT

Input of the standard signal input
for the set-point default

4 to 20 mA

Table 15:

Basic function of communications software

The

INPUT, CUTOFF and CHARACT functions can be parameterized via the communications software.

The instructions for the communications software describe in detail the individual menu options, as well as
parameterization and configuration.
These instructions can be found on the internet at

www.burkert.com

Documentation Type 8791

and

are also available on CD which can be ordered by quoting identification number 804625.

english

Type 8791