Required for analogue output option only), Terminal assignment for operating voltage – Burkert Type 8791 User Manual
Page 53

53
Electrical connection
13.3.4. Terminal assignment for output signals to the control
centre (e.g. plc) (required for analogue output option only)
terminal configuration
On the device side
external circuit / signal level
31 +
Analogue feedback +
31 +
+ (0/4 – 20 mA)
not galvanically isolated
32 –
Analogue feedback GND
32 –
GND (identical with the GND supply
voltage)
Table 27:
Terminal assignment; output signals to the control centre
13.3.5. Terminal assignment for operating voltage
terminal configuration
external circuit / signal level
+24 V
Operating voltage +
+24 V
GND
24 V DC ± 10%
max. residual ripple 10%
GND
Operating voltage GND
Table 28:
Terminal assignment; operating voltage
13.3.6. Terminal assignment for external position sensor
(for remote model only)
terminal configuration
On the device side external circuit / signal level
S +
Supply sensor +
S +
+
Remote-
Sensor
Type 8798
11)
S -
Supply sensor –
S –
–
A
Serial interface, A cable
A
A line
B
Serial interface, B-cable
B
B line
11)
Assignment of the wire color see “Table 30”
Table 29:
Terminal assignment; external position sensor
positioner
terminal
Wire color
remote-sensor with cable type 1
Wire color
remote-sensor with cable type 2
S +
brown
brown
S –
white
black
A
green
red
B
yellow
orange
Table 30:
Assignment of the wire color (Remote-Sensor)
english
Type 8791