72 - 8630

O

PERATION

AND

CONTROLLER

FUNCTIONS

Insensitivity range (dead band) of the positioner

Entry of the dead band in %, referred to the scaled stroke range; i.e.

LIM minus LIM (see

function

X.LIMIT). This function assures that the positioner cuts in only above a certain control

difference. The function reduces wear on the solenoid valves in the TOP

Control Continuous and

the pneumatic actuator.

X.CONTRL

Parametrization of the positioner

XXXX

XXXX

Xd1

Xd1

Xd1'

Xd1'

to controller

Dead band

Position
actual value
(POS)

Position setpoint
(CMD)

Control
difference

Parameters of the positioner

Gain factor of the positioner (to close the valve)

Gain factor of the positioner (to open the valve)

End of parametrization of positioner. Jump back to X.CONTRL.

NOTE

If, during execution of

X.TUNE (AUTOTUNE of the positioner), the supplementary function

X.CONTRL is in the main menu, the dead band X.CO DBND is automatically determined in
dependence on the frictional behaviour of the positioning mechanism. The value resulting is
a guide value. It can be readjusted manually.