beautypg.com

Functional deviations from the standard version, Dp explanation of the menu items – Burkert Type 8630 User Manual

Page 126

background image

124 - 8630

P

ROFIBUS

DP

Explanation of the menu items

BUS ADDR

Entry of the device address (default: 3)

ADDR xxx

Values from 0 to 126 can be set with the arrow keys;

confirmation is done with the MANUAL/AUTOMATIC key.

BUS PDI

Selection of the process values that are to be transferred from the TOP Control
Continuous to the control (master).

* PDI. POS

with the MANUAL/AUTOMATIC key, each process value can be either

:

activated (* appears) or deactivated (no * )

* PDI. ERR

For significance of the process values, see table

PDI: Process Data Input

BUS PDO

Selection of the process values that are to be transferred from the control

(master) to the TOP Control Continuous.

* PDO. INP

With the MANUAL/AUTOMATIC key, each process value can be either

:

activated (* appears) or deactivated (no * ).

* PDO. ERR

For significance of the process values, see table

PDO: Process Data Output

BUS FAIL

Activation for movement to saftey position on bus communication failure

SPOS OFF

The actuator moves to the position corresponding to the setpoint last transmitted
(default setting).

SPOS ON

With

SPOS ON set, the following configurations can occur:

Activated menu item SAFEPOS
On error in bus communication, the actuator moves to the position set under
SAFEPOS.
Deactivated menu item SAFEPOS
On error in bus communication, the actuator moves to the end position it would
occupy in the zero voltage condition.

Functional deviations from the standard version

The operating mode can be switched between MANUAL and AUTOMATIC in the process operating level
either with the keypad on the TOP Control Continuous or over the bus.

MANUAL/AUTOMATIC switchover on the keypad is no longer possible when an operating mode (under
“PDO MODE”) is transmitted to the TOP Control Continuous over the bus.