beautypg.com

Bus status display – Burkert Type 8630 User Manual

Page 146

background image

144 - 8630

D

EVICE

N

ET

Bus status display

The bus standard is indicated on the display.

Display
message

Device status

Explanation/problem elimination

BUS OFFL

alternates with

the display
value set

offline

Device is not connected to the bus; the network access
procedure (Duplicate MAC-ID-Test, duration 2 s) has not yet

ended or the device is the sole active network subscriber.
- Is the baud rate correctly set throughout the network?
- Is the bus connection incl. plug in assignment correct?
- Is the voltage supply and bus connection of the other

subscribers correct?

BUS NOCO

alternates with

the set

indication

value

online,

no connection to
Master

Device is correctly connected to the bus, the network access
procedure has been completed without error, but no

connection is established with the Master.

2 dots

left, under the

set indication
value

online,

Explicit Messaging

only

Messaging connection with Master is established. No I/O

connection is in the Established state (no I/O data exchange).

4 dots

left, under the

set indication
value

online,
active I/O connection

An I/O connection is in the Established state (I/O data
exchange).

BUS TIME

alternates with

the set

indication

value

I/O connection

Timeout

An I/O connection is in the TIME OUT state.

- new establishmend of connection by Master; ensure the

I/O data are transferred cyclically, or with confirmedCOS,
the corresponding Acknowledge Messages are sent by the
Master.

BUS CRIT

alternates with

the set

indication

value

critical bus error

Different device with same address in the network, or BUS
OFF
due to communication problems:

- change address of device and restart device.
- error analysis in network with a bus monitor.