Error messages and malfunctions maintenance, Error messages on the lc display, Other malfunctions – Burkert Type 8630 User Manual

Page 154

background image

152 - 8630

M

AINTENANCE

AND

ERROR

CORRECTION

ON

THE

POSITIONER

Error messages on the LC display

When operated according to these Operating Instructions, the TOP Control Continuous is
maintenance free.

Error messages and malfunctions

Maintenance

Error message on switching on

Error message on execution of the function

X.TUNE

Display

Causes of error

Remedy

X.ERR 1

No compressed air connected

Connect compressed air

X.ERR 2

Compressed air failure during

AUTOTUNE

Check compressed air supply

X.ERR 3

Actuator or positioning system leaky
on exhaust side

None, device faulty

X.ERR 4

Actuator system leaky on pressurized
side

None, device faulty

X.ERR 6

The end positions for POS-MIN and

POS-MAX are too near to each other

Check whether the allocation of the end
positions to POS-MIN and POS-MAX via

the function TUNE-POS is correct.

If incorrect:
Execution TUNE-POS again.
If correct:

TUNE-POS with this arrangement of the

end positions is not possible since they
are too close together.

X.ERR 7

False allocation of POS-MIN and POS-
MAX

To determine POS-MIN and POS-MAX,

move the actuator in each case in the
direction shown on the display.

Other malfunctions

Problem

Possible causes

Remedy

POS = 0 (with CMD > 0 %) or

Tight-closing function

Deactivate tight-closing

POS = 100 %, (by CMD < 100 %)

(CUTOFF)

function

has been inadvertently activated

Display

Causes of error

Remedy

CMD FAUL

signal error

check signal

set-value positioner

EE FAULT

EEPROM faulty

none, device faulty