Factory settings on the top control continuous – Burkert Type 8630 User Manual
Page 32
30 - 8630
S
YSTEM
D
ESCRIPTION
Factory settings on the TOP Control Continuous
Function
Factory setting
ACTFUNC
FUNCSNGL
INPUT
INP 4'20 A
CHARACT
CHA LIN
DIR.CMD
DIR.CRISE
CUTOFF
CUT 0 %, CUT
100 %
DIR.ACT
DIR.ARISE
SPLTRNG
SR
0 (%),
SR 100 (%)
X.LIMIT
LIM
0 %,
LIM
100 %
X.TIME
T.OPN
Values calculated by
AUTOTUNE
T.CLS
Values calculated by
AUTOTUNE
After execution of
SETFACT: 1 s
OUTPUT
OUT ANL:
OUT POS
OUT 4´20 A
OUT BIN:
OUT DEV
DEV 5.0 NO
BIN-IN
B.IN SPOS
SPOS 000 NO
Function
Factory setting
X.CONTRL
X.CO DBND
1 %
X.CO PARA
KX
Values calculated by
AUTOTUNE
KX
Values calculated by
AUTOTUNE
After execution of
SETFACT: 1
P.CONTRL
P.CO DBND
1 %
P.CO PARA
KP
1.00
TN
999.9
TV
0.0
X0
0
P.CO SETP
SETP INT
P.CO INP
INP 4´20 A
P.CO FILT
0
P.CO SCAL
PV 000.0, PV 100.0
P.CO TUNE
D’ACT
P.CO KV
FACT
P.CONTRL with flow rate controller
P.CO DBND
1 %
P.CO PARA
KP
1.0
TN
999.9
TV
0.0
X0
0
P.CO SETP
SETP INT
P.CO INP
INP P1’P2
P.CO FILT
0
P.CO SCAL
PV 000.0, PV 100.0
P.TYP
FLOW
UNIT
M3/H
TEMP
MAN
DENS
1.293
DIAM
0025
P.CO TUNE
D’ACT
P.CO KV
FACT
CODE
CODE 0000
NOTE
The functions and factory settings shown in grey are valid for the optional
flow rate control.