Burkert Type 8630 User Manual
Page 157
8630 - 155
M
AINTENANCE
AND
ERROR
CORRECTION
ON
THE
PROCESS
CONTROLLER
Error messages on execution of the function P.Q'LIN
Display
Causes of error
Remedy
Q.ERR 1
No compressed air connected
Connect compressed air
No change in process value
Check process, switch on pump or open
shut-off valve if necessary
Q.ERR 2
Current fixed point of the valve stroke
was not reached because
• Pressure supply failre
• Check pressure supply
during
P.Q’LIN
• No AUTOTUNE was executed
• execute AUTOTUNE
Display
Cause of error
Remedy
L.ERR 1
No admission pressure at the
Switch on compressor before start of
controller unit (> 50 mbar).
leakage measurement.
L.ERR 2
Control does not fully close.
Execute AUTOTUNE.
L.ERR 3
No leakage detectable:
The leakage characteristic must be
the difference between admission
deactivated since the precision of air
pressure and conveying pressure is
flow control cannot be raised.
so low, even at slight valve opening,
that no air leak can be measured.
Whilst the valve is open the delivery
Make sure that the conveying pipe is
pressure is not increased, which
closed and the blocking air is open.
means that no restart points for the
characteristic can be recorded.
Error message on execution of the function LEAK MEAS