8630 - 155

M

AINTENANCE

AND

ERROR

CORRECTION

ON

THE

PROCESS

CONTROLLER

Error messages on execution of the function P.Q'LIN

Display

Causes of error

Remedy

Q.ERR 1

No compressed air connected

Connect compressed air

No change in process value

Check process, switch on pump or open
shut-off valve if necessary

Q.ERR 2

Current fixed point of the valve stroke
was not reached because

Pressure supply failre

Check pressure supply

during

P.Q’LIN

No AUTOTUNE was executed

execute AUTOTUNE

Display

Cause of error

Remedy

L.ERR 1

No admission pressure at the

Switch on compressor before start of

controller unit (> 50 mbar).

leakage measurement.

L.ERR 2

Control does not fully close.

Execute AUTOTUNE.

L.ERR 3

No leakage detectable:

The leakage characteristic must be

the difference between admission

deactivated since the precision of air

pressure and conveying pressure is

flow control cannot be raised.

so low, even at slight valve opening,
that no air leak can be measured.

Whilst the valve is open the delivery

Make sure that the conveying pipe is

pressure is not increased, which

closed and the blocking air is open.

means that no restart points for the
characteristic can be recorded.

Error message on execution of the function LEAK MEAS