background image

8630 - 99

O

PERATING

THE

PROCESS

CONTROLLER

Position of the decimal point for process actual value and setpoint
(Setting range: 0 ... 3).

Manual entry of the K factor for the flow rate sensor

(e.g. from the data sheet for the flow rate sensor)

Position of the decimal point for the K factor (setting range: 0 ... 2)

K factor (setting range: 0 ... 9999)

Setting the desired unit of the flow rate

Upper scaling value for process setpoint;

the value is assigned to the maximum current or voltage value of the standard
signal. This setting is active only when

P.CO SETP / SETP EXT has been

selected.

Lower scaling value for process setpoint;

the value is assigned to the minimum current or voltage value of the standard
signal. This setting is active only when

P.CO SETP / SETP EXT has been

selected.

Upper scaling value for process actual value;

the value is entered in the unit that is subsequently selected for the flow rate. This
setting determines the reference span for the dead-band of the process controller
and the analog feedback of the process actual value (option).

Lower scaling value for process actual value;

the value is entered in the unit that subsequently selected for the flow rate. This
setting determines the reference span for the dead-band of the process controller
and the analog feedback of the process actual value (option).