Other malfunctions – Burkert Type 8630 User Manual
Page 158

156 - 8630
M
AINTENANCE
AND
ERROR
CORRECTION
ON
THE
PROCESS
CONTROLLER
Other malfunctions
Problem
Possible causes
Remedy
POS = 0 (with CMD > 0%) or
Tight-closing function
Deactivate tight-closing
POS = 100%,(with CMD < 100%) (CUTOFF) has
function
PV = 0 (with SP > 0) or
been inadvertently activated
PV = PV (with SP > SP )
Only with devices with analog
repeat:
red LED does light
Binary output:
Check connection of
Current > 100 mA
binary output
Binary output does not switch
short circuit
Only with devices with process
controller:
Device does not work as a
Menu item
P.CONTRL stands in
Remove the menu item
controller despite correctly
main menu. The device thus
P.CONTRL from the main
executed settings.
works as a process controller
menu.
and expects a process value at
the corresponding input.
- Type 0125 (15 pages)
- Type 0121 (4 pages)
- Type 0331 (4 pages)
- Type 6012 (4 pages)
- Type 0330 (2 pages)
- Type 0127 (18 pages)
- Type 0131 (5 pages)
- Type 0141 (5 pages)
- Type 0142 (12 pages)
- Type 0145 (3 pages)
- Type 0174 (5 pages)
- Type 0212 (2 pages)
- Type 0211 (5 pages)
- Type 0212-B (18 pages)
- Type 0250 (64 pages)
- Type 0253 (2 pages)
- Type 0255 (15 pages)
- Type 0355 (2 pages)
- Type 0255 (2 pages)
- Type 8006 (34 pages)
- Type 8640 (2 pages)
- Type 8640 (55 pages)
- Type 8640 (119 pages)
- Type 0256 (15 pages)
- Type 0256 (2 pages)
- Type 0258 (72 pages)
- Type 0262 (5 pages)
- Type 0273 (6 pages)
- Type 0280 (2 pages)
- Type 0280 (12 pages)
- Type 0280 (5 pages)
- Type 0281 (2 pages)
- Type 0282 (2 pages)
- Type 0283 (2 pages)
- Type 0286 (4 pages)
- Type 0287 (15 pages)
- Type 0290 (2 pages)
- Type 0290 (14 pages)
- Type 0293 (18 pages)
- Type 0300 (6 pages)
- Type 0301 (6 pages)
- Type 0312 (6 pages)
- Type 0311 (2 pages)
- Type 6519 (3 pages)
- Type 6519 (4 pages)