Safety settings on bus failure
The actuator moves to the position corresponding to the setpoint last transmitted (default setting).
For other setting options (see the chapter
Settings on the TOP Control Continuous)
Drop line length (Drop Lines)
Technical data
EDS file
BUER8630.EDS
Icons
BUER8630.ICO
Baud rate
125 kBit/s, 250 kBit/s, 500 kBit/s (adjustable via keys at the device or via
network);
Factory setting 125 kBit/s
Adress
0 ... 63; (adjustable via keys at the device or via network);
Factory setting 63
Process data
7 static Input Assemblies
(Input: from TOP
Control Continuous to DeviceNet Master/Scanner)
4 static Output Assemblies
Total line length according to DeviceNet specification
(Total line length = sum of all mein and drop lines)
Baud rate
Maximum total line length
Thick Cable
Thin Cable
125 kBaud
500 m
100 m for all baud rates
250 kBaud
250 m
500 kBaud
100 m
Baud rate
Length of drop lines
Maximum length
Maximum total length of drop lines in network
125 kBaud
6 m for all baud rates
156 m
250 kBaud
78 m
500 kBaud
39 m