Effect of limitation of the opening speed after a step in the setpoint
X.TIME
Limitation of the correcting speed
Factory setting: 1 s
Opening time for full stroke (in seconds)
Closing time for full stroke (in seconds)
If the correcting speed is to be limited, values can be entered for
T:OPN and T.CLS that lie between the
minimum values determined by
X:TUNE and 60 s.
NOTE
When executing the function
X.TUNE, the minimum opening and closing time for T.OPN
and
T.CLS is automatically entered for the full stroke. In this way it is possible to traverse at
maximum speed.
XX
XX
Valve stroke [%]
(POS, CMD)
Setpoint
Actual
value
T.OPN
t
NOTE
If positioning times < 1 s are determined from the
AUTOTUNE, X.TIME is automatically
copied to the main menu and the relevant value is set to 1 s.
- Type 0125 (15 pages)
- Type 0121 (4 pages)
- Type 6012 (4 pages)
- Type 0330 (2 pages)
- Type 0331 (4 pages)
- Type 0127 (18 pages)
- Type 0131 (5 pages)
- Type 0141 (5 pages)
- Type 0142 (12 pages)
- Type 0145 (3 pages)
- Type 0174 (5 pages)
- Type 0212 (2 pages)
- Type 0211 (5 pages)
- Type 0212-B (18 pages)
- Type 0250 (64 pages)
- Type 0253 (2 pages)
- Type 0255 (15 pages)
- Type 0355 (2 pages)
- Type 0255 (2 pages)
- Type 8640 (2 pages)
- Type 8640 (55 pages)
- Type 8640 (119 pages)
- Type 8006 (34 pages)
- Type 0256 (15 pages)
- Type 0256 (2 pages)
- Type 0258 (72 pages)
- Type 0262 (5 pages)
- Type 0273 (6 pages)
- Type 0280 (12 pages)
- Type 0280 (5 pages)
- Type 0280 (2 pages)
- Type 0281 (2 pages)
- Type 0282 (2 pages)
- Type 0283 (2 pages)
- Type 0286 (4 pages)
- Type 0287 (15 pages)
- Type 0290 (2 pages)
- Type 0290 (14 pages)
- Type 0293 (18 pages)
- Type 0300 (6 pages)
- Type 0301 (6 pages)
- Type 0312 (6 pages)
- Type 0311 (2 pages)
- Type 6519 (3 pages)
- Type 6519 (4 pages)