Table b-12: slope thermal compensation, B - 5, Table b-13: call-out – GE Industrial Solutions Galaxy Vector Controller GCM3 User Manual
Page 97: Table b-14: serial ports

Galaxy Vector Controller GCM2, GCM3
Issue 4 January 2008
T1.317 Objects and Attributes Appendix B - 5
Table B-12: Slope Thermal Compensation
Related Commands
OBJ,ATTR
DESCRIPTION
STA
CHA
OPE
TYPE
RANGE OF VALUES
sc1,stt
State
√
√
number
0:disable 1:enable
sc1,rve
Raise voltage enable
√
√
number
0:disable 1:enable
sc1,ltt
Lower temperature
√
√
number
-5-20:0°C
sc1,ntt
Nominal temperature
√
√
number
15-30:25°C
sc1,utt
Upper temperature
√
√
number
30-55:45°C
sc1,spt
Step temperature threshold
√
√
number
45-85:75°C
sc1,lsp
Lower temperature slope
per cell
√
√
number
1-5:3mV/°C
sc1,usp
Upper temperature slope
per cell
√
√
number
1-5:3mV/°C
Table B-13: Call-Out
Related Commands
OBJ,ATTR
DESCRIPTION
STA
CHA
OPE
TYPE
RANGE OF VALUES
p1,phn
Primary phone number
√
√
text
Up to 25 characters:“”
a1,phn
Alternate phone number
√
√
text
Up to 25 characters:“”
Table B-14: Serial Ports
Related Commands
OBJ,ATTR
DESCRIPTION
STA
CHA
OPE
TYPE
RANGE OF VALUES
mp1,bdr
Modem baud rate
√
√
number
1200,2400,4800,9600, and 19200
mp1,ins
Modem initialization string
√
√
text
Up to 25 characters: “at&fev&c1h0”
mp1,hsh
Modem handshaking
√
√
text
“NO”: none
“SW”: xon and xoff
mp1,nrg
Modem number of rings
before answering
√
√
number
1 - 9 rings
lp1,bdr
Local RS-232 baud rate
√
√
number
“AUTO”,1200,2400,4800,9600,
and 19200
lp1,hsh
Local RS-232 handshaking
√
√
text
“NO”: none
"SW": xon and xoff
"HW": cts and rts