Operation, Office alarm contacts, Alarm descriptions – GE Industrial Solutions Galaxy Vector Controller GCM3 User Manual
Page 35: 3 operation, 3operation

Galaxy Vector Controller GCM2, GCM3
Issue 4 January 2008
Operation 3 - 1
3
Operation
Office Alarm 
Contacts
The basic Galaxy VC issues PMJ, PMN, MJF, BD, ACF and 
HV/2ACF/VLV office alarms off the BLJ3 and BTJ2/BTJ3 
boards. Refer to Table 2-G and 2-N, respectively, for a 
description of their output terminals. Refer to Table 3-A for a 
listing of the various available alarms. Refer to Table 3-B for a 
listing of alarm relays and their associated front panel LEDs.
Alarm 
Descriptions
To see active alarms, press the Active Alarm softkey, then use 
the 
∧ or ∨ keys to page through alarms. See Tables 3-A and 3-B.
The alarms are listed in order of severity. Some abbreviations are 
required to fit the LCD screen.
Very Low Voltage Alarms and Battery on Discharge 
When rectifier output is insufficient to maintain the load current 
at the set voltage (typically because of an ac power failure), the 
plant bus voltage drops. When this voltage drops below the 
battery voltage, the batteries start providing current to the load. 
Any time that the plant voltage is below the threshold selected 
for BD, the Battery on Discharge alarm activates. If the plant 
voltage continues to drop, a second, lower threshold can be 
reached, activating a Very Low Voltage alarm. Default values 
for these thresholds are set at the factory. These thresholds can 
be changed by the operator in the configuration menu as 
described in the Installation and Configuration section of this 
manual (Section 4). S1.5 set to “1” will allow the relay dedicated 
for HV/ACF/VLV, K8, to be asserted for the VLV condition.
Note that a BD alarm does not necessarily mean that the batteries 
are discharging, only that the present voltage is lower than the 
set point for this alarm. This alarm may be activated by an 
incorrectly set BD threshold or plant voltage set point. 
