Table 3-B: Office Alarm Relay and Front Panel LED Standard Assignments
Asserted Condition
Alarm Relays
Front Panel LEDs
Very high voltage [HV]
PMJE, (HV or none)
MAJ (red)
High float voltage [HFV]
PMNE
MIN (yellow)
Battery on discharge [BD]
PMJE, BD
MAJ (red)
Very low voltage [VLV]
PMJE, (VLV or none)
MAJ (red)
Single ac fail [ACF]
PMNE, ACF
MIN (yellow)
Multiple ac fail [MACF]
PMJE, (2ACF or none)
MAJ (red)
Single rectifier fail [RFA]
PMNE
MIN (yellow)
Multiple rectifier fail [MRFA]
PMJE
MAJ (red)
Single converter fail [CFA]
PMNE
MIN (yellow)
Multiple converter fail [MCFA]
PMJE
MAJ (red)
Major fuse (Controller, FAJ input) [MJF]
PMJE, MJF
MAJ (red)
Low voltage battery disconnect [LVBD]
PMJE
MAJ (red)
Low voltage load disconnect [LVLD]
PMJE
MAJ (red)
LVD1 fail [LVDA]
PMJE
MAJ (red)
LVD2 fail [LVDA]
PMJE
MAJ (red)
Controller fail [CTLR]
PMJE
MAJ (red)
Slope thermal compensation active
LCD
Defective battery temperature probe [TPA]
PMNE
MIN (yellow)
Voltage sense fuse alarm
PMJE
MAJ (red)
Rectifier manual off alarm
PMNE
MIN (yellow)
Rectifier phase alarm
PMNE
MIN (yellow)
Rectifier half power alarm
PMNE
MIN (yellow)
Auxiliary major alarm
PMJE
MAJ (red)
Battery thermal alarm
PMJE
MAJ (red)
Controller unpowered
PMJE, PMNE, MJF, BD,
ACF, HV
Connector open
PMJE, PMNE
MAJ (red)
Alarm cut off
LCD
Display volts
LCD
Display amps
LCD
Galaxy Vector Controller GCM2, GCM3
3 - 4 Operation
Issue 4 January 2008
High Float Voltage Minor Alarm and Very High Voltage
Major Alarm and Shutdown
Because of the importance of protecting the batteries and load
from overvoltage conditions, three high voltage thresholds are
provided. Two are controlled by the Vector and one backup
threshold is hard-wired internally in Lineage Power rectifiers.