beautypg.com

Powerware 9170+ User Manual

Page 83

background image

Specifications

79

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

Table 14. Environmental and Safety

Operating Temperature

0°C to 40°C (32°F to 104°F)

Optimal battery performance: 25°C (77°F)

Storage Temperature

UPS with battery modules: ć20°C to +40°C (ć4°F to 104°F)

UPS without batteries: ć40°C to +60°C (ć40°F to 140°F)

Relative Humidity

5ć95% noncondensing

Operating Altitude

Up to 3,050 meters above sea level (10,000 ft)

The maximum operating ambient temperature decreases 1°C per 300m above 1525m

(2°F per 1000 ft above 5000 ft)

Non-Operating Altitude

Up to 12,200 meters above sea level (40,000 ft)

Ventilation

The air around the UPS must be clean and free of dust, corrosive chemicals, and other

contaminants. The Powerware 9170 UPS uses internal fans to circulate the air for cooling.

The air must be free to circulate around the UPS and battery cabinet(s). Do not operate the

UPS in a sealed room or container.

Audible Noise

Less than 53 dBA

Surge Suppression

ANSI C62.41 Category B (formerly IEEE 587); IEC 61000-4-5

Safety Conformance

CAN/CSA C22.2, No. 107.1; UL 1778;

EN 50091-1-1 and IEC 60950

Agency Markings

UL, cUL, TÜV, CE, C-Tick, BCIQ

EMC (Class A)

EN 50091-2, FCC Part 15, ICES-003, VCCI

Table 15. Battery

Configuration

(2) 60V, 7.2 Ah batteries per string

Voltage

120 Vdc

Type

Sealed, maintenanceĆfree, valveĆregulated, leadĆacid

Charging

Recharge time: 4 hr after full-load resistive discharge; 8 hr after half-load resistive

discharge, using standard internal battery charger.

Optional battery chargers at higher current ratings will be available for future product

release.