beautypg.com

Powerware 9170+ User Manual

Page 61

background image

UPS Startup

57

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

4. The output voltage is the most important operating parameter

you must set as part of the initial configuration screens. Select

the desired UPS output voltage using the

Y

and

B

buttons.

Possible selections are 200, 208, 220, 230, and 240 Vac. (Low

voltages are derived from these voltages, as listed in Table 5 on

page 35 and Table 6 on page 43.) Press the button when the

desired output value is displayed.

5. If the system includes any external battery cabinets, record the

ampere-hour capacity of batteries installed in these cabinets.

Count the number of battery strings (two battery modules,

side-by-side equals one string). Each battery string contains

7.2 ampere-hours. Enter the total value in the next startup

screen.

External Capacity

extamphr 0028.8

<– –> ESC

6. The system signals an alarm when required output cannot be

maintained with the loss of redundant power modules. The

alarm is essentially disabled with a redundancy level set at 0.
If you want the system to notify you when the number of

redundant power modules is less than a specified level, enter a

redundancy level. Each increment above 0 indicates the

number of modules that can be removed from operation before

the alarm occurs. This setting only affects the alarm; the system

continues to operate as an N+X system even if this parameter is

left at the default value of 0.

Set Redundancy

RSetting 0

<– –> ESC