Dedicated Input Signals

Emergency Power-Off (EPO):

Connection to a facility Emergency Shutdown

switch provides a method for emergency Powerware 9170 system

shutdown. Opening this connection creates an immediate shutdown of

the Powerware 9170 UPS output.

Bypass:

The signal from an external bypass switch, to isolate the

Powerware 9170 system for maintenance purposes, tells the UPS to go

into Internal Bypass mode.

On-Generator:

An external signal that the input power is being supplied

by a generator tells the UPS to accept wider input power frequency

limits.
See Figure 21 on page 31 and Figure 24 on page 34 to make the

connection for all dedicated input signals.

DB-9 Port Pin Functions

Table 10 explains the functions of the pins on the Powerware 9170 DB-9

port. This port is on the Powerware 9170 UPS rear panel, as shown in

Figure 42 on page 52.

Table 10. DB-9 Port Signals

Pin

Function

Description

1

RS-232 Receive Data

Receives incoming RS-232 communication data. The data protocol is 9600 baud, 8 bits,

no parity, 1 stop bit, no handshaking.

NOTE

In battery operation, a 5-second +Vdc (RS-232 low) signal applied to this pin

causes the UPS to shut down after a delay of X minutes, regardless of the return of AC

input power. This time is defined by the External Shutdown mode parameter n, where n

and X are related as follows:

n

X

n

X

n

X

0

2

3

3

6

20

1*

2

4

5

2

1

5

10

* For n=1, the UPS stays off when AC input power returns. For all other values of n, the

UPS restarts 12 seconds after AC input power returns.

2

RS-232 Transmit Data

Sends outgoing RS-232 communication data. The data protocol is 9600 baud, 8 bits, no

parity, 1 stop bit, no handshaking.

3

Normally-Open

On-Battery Contact*

A normally open contact that closes (pulls to Common) 15 seconds after the UPS

switches to battery power.

4

Common

The ground reference for all input and output signals.