Electrical Installation

28

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

Table 3. Bypass Switch Positions

Switch Position

Description

LINE

Connects the load directly to AC input power and disconnects UPS output. AC input power is still

connected to the UPS input.

OFF

Disconnects the load from the UPS output power and AC input power, as well as AC input power

to the UPS input.

UPS

Connects the UPS output to the load.

SERVICE

Like the LINE position, SERVICE connects the load directly to AC input power and disconnects

UPS output. However, because SERVICE also disconnects AC input from the UPS, this is

the appropriate position for UPS maintenance or repair.

To disconnect AC input power during maintenance or service, turn the

bypass switch to the SERVICE position. For MBB switches, you must

press the red button beside the switch before you can change the switch

position.
There are six bypass switch models available for the Powerware 9170

UPS as specified in Table 4.

Table 4. Bypass Switch Specifications

Bypass Switch Models

R ti

See Figure 20

BBM

MBB

Rating,

Continuous

Height

Width

Depth

Mounting Centers

Weight

Continuous

(A)

(B)

(C)

(D)

(E)

BPE12BBM1A BPE12MBB1A

40A/300 Vac

(CSA)

50A/300 Vac

(UL,TÜV)

21.0I

(534 mm)

14.0I

(356 mm)

6.8I

(172 mm)

11.0I

(280 mm)

20.0I

(508 mm)

27 lb

(12.3 kg)

BPE14BBM1A BPE14MBB1A

80A/300 Vac

21.0I

(534 mm)

14.0I

(356 mm)

6.8I

(172 mm)

11.0I

(280 mm)

20.0I

(508 mm)

31 lb

(14.1 kg)

BPE22BBM1A BPE22MBB1A

150A/300 Vac

26.5I

(673 mm)

18.4I

(467 mm)

6.6I

(168 mm)

16.0I

(406 mm)

25.5I

(648 mm)

53 lb

(24.1 kg)