Communication

72

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

Description

Function

Pin

5

Normally-Open

Low-Battery-Alarm

Contact*

A normally open contact that closes (pulls to Common) to signal a Near Low Battery or

Low Runtime alarm. Values that affect this contact closure may be user-programmed.

6

Reserved

Reserved

7

Immediate Shutdown

Mode

Set by External Shutdown parameter, n = 0:

Grounding this pin for 5 seconds causes the UPS to switch immediately to the Off

mode. When AC input power returns, the UPS will not restart without user intervention.

Remote Shutdown

Mode

Set by External Shutdown parameter, n = 1 or greater:

In battery operation, grounding this pin for 5 seconds causes the UPS to shut down

after a delay of X minutes, regardless of the return of AC input power. This time is

defined by the External Shutdown mode parameter n, where n and X are related as

follows:

n

X

n

X

1

2

4

5

2

1

5

10

3

3

6

20

8

Normally-Closed

On-Battery Contact

A normally closed contact that opens (releases from Common) 15 seconds after the UPS

switches to battery power.

9

Normally-Open

Bypass-Switch-Status

Contact*

A normally open contact that closes (pulls to Common) whenever the UPS is in internal

bypass mode or is being externally bypassed and is being signalled of the external

bypass.

*Contacts consist of open-collector circuits capable of switching up to +40 Vdc, 50 mA resistive load.