Maintenance

74

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

Storage Temperature

Store the Powerware 9170 battery modules (in the unit or battery

cabinet) at ć20 to +40°C (ć4 to +104°F). Batteries will have a longer

shelf life if they are kept below +25°C (+77°F). The Powerware 9170

UPS or battery cabinet without batteries may be stored at ć40 to +60°C

(ć40 to +140°F).

External Bypass Switch (Make-Before-Break Only) Operation

Before turning the Powerware MBB bypass switch, you must press the

red button located next to the handle. This button serves two purposes.

It sends an electrical signal to the UPS to switch to the internal Bypass

mode (if it is not already operating in that mode). The button also

operates a mechanical interlock, to prevent the switch from being

turned without first signaling the UPS.

NOTE When the red button is released, the UPS remains in its internal Bypass mode

and must be manually returned to the Auto mode by selecting that mode on the front

panel display.

Battery Replacement

The Powerware 9170 hotĆswappable feature allows you to replace the

battery modules easily without disconnecting the load or damaging the

batteries.

NOTE The Powerware 9170 UPS will operate with uncharged (or no) batteries, but

will have limited (or no) battery backup capability. Backup protection requires at least

three battery strings for every four power modules.

Use the following procedure to replace battery modules in pairs.

1. Remove the front panel bezel(s) covering the battery modules

you need to replace. Label the original module with masking

tape or some other identifier.

2. Grasp the battery module handle and press down on the latch

release.

3. Pull the module out approximately 7I (17 cm) to the secondary

stop on top of the module.