Moving the cabinets – Powerware 9170+ User Manual
Page 19
![background image](/manuals/184233/19/background.png)
Installation Setup
15
Powerware
®
9170 User's Guide
S
LTM-1344 B Uncontrolled Copy
Mounting Centers for 5/16I (8-mm) Floor Bolts
Dimension (see Figure 12)
Measurement
A
14.5I (36.8 cm)
B (3- and 6-slot cabinets)
30.25I (76.8 cm)
B (9- and 12-slot cabinets)
34.25I (87 cm)
B
A
Floor Anchor
Bracket
Figure 12. Floor Anchor Brackets Bolted to UPS Cabinet
Moving the Cabinets
The Powerware 9170 UPS and the battery cabinet are very heavy with
power and battery modules installed. Before moving the cabinets,
remove the power and battery modules and move these modules
separately from the cabinets.
The smaller (3- and 6-slot) cabinets may be ordered with a caster cart, to
enable moving the cabinet. Caster Cart Installation" on page 10
describes how to set the four foot pads on this cart to keep the cabinet
from rolling when properly positioned.
The larger (9- and 12-slot) cabinets have casters built into the cabinet
base. Use the following procedure to raise the cabinet before rolling it
on its casters. For 12-slot cabinets that do not have output isolation, see
Stabilizer Bracket Installation" on page 11, for details about mounting
stabilizer brackets before rolling the cabinet into place.
1. Ensure that the cabinet contains no power or battery modules.
2. Locate the four plastic caps covering the caster bolts. They are
at the corners of the cabinet base.