beautypg.com

Neutral-to-ground bonding for isolated output – Powerware 9170+ User Manual

Page 48

background image

Isolated Output Wiring Diagrams

44

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

100, 110,

115, or 120

X2

50 or 60 Hz

100/200, 110/220, 115/230, or 120/240V Out

with Isolated Output Option

Parameter 7-3-4 set to 200, 220, 230, or 240, as required.

X1

X3

X

X

N-G Bond

L2

N

X

L1

200, 220, 230, or 240

100, 110,

115, or 120

X0

Figure 34. Isolated Outputs ć Single-Phase Voltages

X2

50 or 60 Hz

120/208 or 127/220V Out

with Isolated Output Option

Parameter 7-3-4 set to 208 or 220, as required.

X1

X3

X

X

N-G Bond

L2

N

X

L1

208 or 220

120 or 127

X0

88 or 93

Figure 35. Isolated Outputs ć Derived 3-Phase Voltages

Neutral-to-Ground Bonding for Isolated Output

As required under safety regulations issued by various regulatory

agencies, the UPS cabinet must have a ground-bond connection for the

neutral terminal of an isolated-output system. In such a system, the

customer must make the neutral-to-ground (also referred to as N-G or

neutral-to-earth) connection after selecting the desired output

configuration.
In isolated-output systems, a green and yellow neutral-to-ground

bonding wire is supplied, with one end connected to the ground (earth)

UPS terminal as shown in Figure 36. The other end of the wire (as

shown by * in Figure 36) must be attached to the proper output neutral

terminal, as specified in Figure 34 and Figure 35.