Maintenance

75

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

4. Press down on the secondary stop release, pull the module out

further, and support the module weight with your second hand

as you remove the module from the cabinet. Remove the

battery module beside the first in a similar manner.

5. After removing a pair (one string) of battery modules, install a

replacement pair. Replacements may be installed in empty

cabinet slots before removing original battery modules.

6. When all desired battery modules have been replaced, reinstall

the front panel bezel(s).

Power Module Replacement

The Powerware 9170 hotĆswap feature allows you to replace a power

module easily without disconnecting the load or damaging the UPS.

NOTE The UPS may switch to internal bypass if the remaining power modules are

insufficient to supply the required power. If empty slots exist, install replacement

modules before removing original ones.

Use care in removing and installing power modules. To remove a power

module:

1. Loosen the thumbscrew on the module handle. Press down on

the latch release at the center of the module handle and pull the

handle down.
As the handle fully extends, the module disconnects. Slide the

module slowly out of the cabinet.

2. Use two hands to support the module. When fully extended,

lower the front down slightly and lift the rear edge over the

safety stop on the center support rail.

3. Treat the original and replacement modules with care to avoid

damaging connectors or internal circuitry. Label the original

module with masking tape or some other identifier. Record the

serial number of the replacement module for your warranty.