The following notes are referenced in the non-isolated system wiring

diagrams (Figure 28 through Figure 33). To determine which diagram is

correct for your site, see Table 5 on page 35.

NOTE 1 The customer must provide input overcurrent protection as stated in NEC

Section 240-21 or local codes. Size the protection device according to local code

requirements (see Table 1 on page 26).
NOTE 2 The UPS bypass switch must be installed within sight of the UPS. To properly

install, complete the voltage and phase check procedure in Startup for Hardwired

Units" on page 53. The wires coming from the side of the switch must be connected as

described in Step 10 on page 33.
NOTE 3 All AC circuit conductors, including the neutral and equipment grounding

conductors, must be the same size (ampacity), have the same rating (75°C) copper

wire, and be sized according to the input circuit breaker. The UPS input and output

conductors must be run through separate conduits.
NOTE 4 The customer must provide output overcurrent protection. See NEC

Section 240-21 or local requirements. See Table 13 on page 78 for maximum

output overcurrent protection device ratings.
NOTE 5 See Equipment Clearances" on page 7 for installation and service

clearances before installing the UPS. Use flexible conduit on the UPS or the external

battery cabinet if either must be moved.
NOTE 6 External UPS battery cabinets are optional. See Battery Cabinet Installation"

on page 17 for installation instructions.
NOTE 7 UPS output circuits shall be installed in dedicated conduit systems and not

shared with other electrical circuits.