Page 47: Iagrams

background image

43

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

C H A P T E R

5

I

SOLATED

O

UTPUT

W

IRING

D

IAGRAMS

The wiring diagrams in this section are unique and specific to

installations in which the output of the Powerware 9170 UPS is

galvanically isolated from the input.
Figure 37 through Figure 40 describe output wiring configurations for

various output voltages. Use Table 6 to find the desired wiring diagrams

and connect the output AC wiring to the proper Powerware 9170 system

power terminals. You must also set the operating menu parameter 7-3-4

for the required output voltage as shown in the wiring configuration

drawings.

NOTE For isolated outputs, all power modules in the Powerware 9170 UPS cabinet

must be split-phase modules, which have blue labels.
NOTE In isolated-output installations, connect the UPS green and yellow

neutral-to-ground wire (N-G bond) to UPS output terminal as illustrated in Figure 36 on

page 45.

Table 6. Wiring Diagrams for Isolated Output

UPS Input

UPS Output

Output Wires

External

Wiring Diagrams

UPS Input

Voltage

UPS Output

Voltage

Output Wires

External

Bypass

Input

Output

System

100/200

110/220

115/230

100/200

110/220

115/230

L1 L2 N*

Yes

Figure 25a

Figure 34

Figure 37

115/230

120/240

120/208**

115/230

120/240

120/240

L1, L2, N*

No

Figure 25a

Figure 34

Figure 38

120/208**

120/208

L1 L2 N*

Yes

Figure 25a

Figure 35

Figure 39

120/208

127/220**

120/208

127/220

L1, L2, N*

No

Figure 25a

Figure 35

Figure 40

*Split-phase power modules required.
**External bypass switch, if installed, must be Break-Before-Make.