beautypg.com

Bypass switches – Powerware 9170+ User Manual

Page 31

background image

Electrical Installation

27

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

Table 2. Recommended Wire Sizes

Input Circuit Breaker Size

75°C Copper Wire Size

Conductor Screw Torque

25A

10 AWG (5.3 mm

2

)

20 in lb (2.3 Nm)

40A

8 AWG (8.4 mm

2

)

25 in lb (2.8 Nm)

60A

4 AWG (21.2 mm

2

)

35 in lb (4.0 Nm)

80A

3 AWG (26.7 mm

2

)

45 in lb (5.1 Nm)

100A

2 AWG (42.1 mm

2

)

55 in lb (6.2 Nm)

125A

1/0 AWG (53.5 mm

2

)

65 in lb (7.3 Nm)

FOR U.S. INSTALLATIONS, READ THIS IMPORTANT NOTE!

This table lists the AWG and mm

2

wire size for each circuit breaker size shown on the wiring diagrams. The minimum

recommended circuit breaker sizes for each model and voltage application are listed on the wiring diagrams.

Conductor sizes shall be no smaller than the 75°C wire size based on the ampacities given in Table 310ć16 of the National

Electrical Code, ANSI/NFPA 70-1999, and article 220. All circuit conductors, including the neutral and equipment grounding

conductors, must be the same size (ampacity) wire. Code may require a larger AWG size than shown in this table because

of temperature, number of conductors in the conduit, or long service runs. Follow local code requirements.

Bypass Switches

Bypass switches are available in two types: Make-Before-Break (MBB)

and Break-Before-Make (BBM).
An MBB switch makes a new connection before it breaks the original

connection. For example, if you turn an MBB switch from UPS to LINE,

the bypass switch connects the load to AC input power before

disconnecting the load from UPS output power. (As noted in Figure 37

on page 47, MBB switches may not be used in certain system

configurations.)
A BBM switch breaks the original connection before it makes a new one.

If you turn a BBM switch from UPS to LINE, the switch disconnects the

load from UPS output power before connecting the load to AC input

power.
The bypass switch has four positions as described in Table 3.

NOTE In the UPS or LINE position, AC input power is still connected to the input

terminals inside the UPS.