Electrical Installation

30

Powerware

®

9170 User's Guide

S

LTM-1344 B Uncontrolled Copy

UPS Installation with an External Bypass Switch

W

A

R

N

I

N

G

Only qualified service personnel (such as a licensed electrician) should perform the

electrical installation. Risk of electrical shock.

C

A

U

T

I

O

N

To prevent electrical shock or damage to the equipment, verify that the Powerware

9170 UPS is OFF before you remove the entrance panel. The circuit breaker or

disconnect switch must also be off at the AC input service panel. Also, turn OFF the AC

disconnect and bypass switches before you connect any wires to the bypass switch

terminal strip.

1. Mount the bypass switch within sight of the UPS. If you do not

have a Powerware bypass switch or the fuse box or panel is out

of sight, you must install a separate disconnect switch next to

the UPS.
The bypass switch should be mounted securely to a sturdy

surface. You may need to turn the cabinet 90 degrees (on its

side) to enable operator access to the switch handle.

2. Remove the six screws in the bypass switch front panel and

remove the panel. Remove any packing material inside the

bypass switch.
Remove knockouts in the bottom of the bypass switch for AC

Line Input, AC to UPS Input, AC from UPS Output, and AC to

the UPS load.