Schneider Electric 890USE17700 User Manual
Page 74

STB NIP 2212 Web Server
74
890USE17700 April 2004
Assigning a
Configured
IP Address to the
STB NIP 2212
Use the following procedure to configure an IP address for the STB NIP 2212. Note:
Your STB NIP 2212 cannot have a role name.
Step
Action
Comment
1
Set the lower rotary switch to an INTERNAL
position (See Physical Description, p. 28),
and power cycle the STB NIP 2212.
2
If your STB NIP 2212, has a role name, you
must remove it using the Role Name web
page (See Configuring a Role Name, p. 82).
If no role name is assigned, skip
step 2.
3
Open the STB NIP 2212 web site.
4
Click on the Configuration tab to display the
Configuration menu.
5
Select the Configured IP option.
6
In the IP address field, type the IP address
that you want to use in dotted decimal
format.
7
Click on the Save button to save the address
to Flash memory and in RAM.
If the address is valid, it will appear in
the banner at the top of each
STB NIP 2212 web page.
Note: The LAN ST LED (See
Ethernet Communications LEDs,
p. 31) on the NIM blinks four times if
the IP address is a duplicate.
8
Click on the Configuration tab to return to the
Configuration menu.
9
Select the Reboot option (See About the
Reboot Option, p. 76).
10
At the Reboot now? prompt, click on the OK
button.
11
Click on the OK button at the confirmation
prompt, "Are you sure?"
Your STB NIP 2212 restarts. The
IP address that you set up on the web
is the active IP address for the island.