Port502 Messaging Subtree

Introduction

Port502 services support TFE services. Port502 services manage explicit client/
server communications that support applications, e.g., HMI data communications.
Every Port502 SAP is associated with a unique object in the Port502 MIB subtree.

Port502 MIB
Subtree

The Port502_Messaging subtree (OID 5) provides connection management and
data flow services to the STB NIP 2212. The following table includes the port502
objects and OIDs used by a TFE service:

Service

Indication for Port 502

Available
Values

port502Status(1)

status of the service

idle
operational

port502 SupportedProtocol(2)

supported protocols

2

port502IPSecurity(3)

status of IP security

disabled–default
enabled

port502MaxConn(4)

max. no. of TCP connections supported 33

port502LocalConn(5)

no. of local TCP connections currently
active

always 0

port502RemConn(6)

no of rport502 connections that are
currently active

0 ... 32

port502 IPSecurityTable(7)

table containing the total no. of
unsuccessful TCP connection attempts
by a remote device

port502ConnTable(8)

table containing Port 502-specific
information

MsgIn
MsgOut

port502MsgIn(9)

total number of Port 502 messages
received from the network

port502MsgOut(10)

total number of Port 502 messages sent
to the network

port502MsgOutErr(11)

total number of error messages sent to
the network from Port 502

port502AddStackStat(12)

support of additional stack statistics

disabled
enabled

port502AddStackStatTable(13) additional stack statistics (optional)