Error Reporting

Each bit in register 45358 indicates a specific global error condition. A value of 1
indicates an error:

1 Fatal error. Because of the severity of the error, no further communications are possible

on the island bus.

2 Module ID error—A standard CANopen device is using a module ID reserved for the

Advantys STB modules.

3 Auto-addressing has failed.

4 Mandatory module configuration error.

5 Process image error—either the process image configuration is inconsistent, or it could not

be set up during auto-configuration.

6 Auto-configuration error—a module is not in its configured location, and the NIM cannot

complete auto-configuration.

7 An island bus management error was detected by the NIM.

8 Assignment error—the initialization process in the NIM has detected a module assignment

error.

9 Internal triggering protocol error.

10 Module data length error.

11 Module configuration error.

12 Timeout error.

15 14 13 12 11 10 9 8

7 6 5 4 3 2 1 0

Register 45358

reserved

see 1

see 2

see 3

see 4

see 5

see 6

see 7

see 8

see 9

see 10

see 11

see 12

reserved