Data Exchange
128
890USE17700 April 2004
Error Reporting
Each bit in register 45358 indicates a specific global error condition. A value of 1
indicates an error:
1 Fatal error. Because of the severity of the error, no further communications are possible
on the island bus.
2 Module ID error—A standard CANopen device is using a module ID reserved for the
Advantys STB modules.
3 Auto-addressing has failed.
4 Mandatory module configuration error.
5 Process image error—either the process image configuration is inconsistent, or it could not
be set up during auto-configuration.
6 Auto-configuration error—a module is not in its configured location, and the NIM cannot
complete auto-configuration.
7 An island bus management error was detected by the NIM.
8 Assignment error—the initialization process in the NIM has detected a module assignment
error.
9 Internal triggering protocol error.
10 Module data length error.
11 Module configuration error.
12 Timeout error.
15 14 13 12 11 10 9 8
7 6 5 4 3 2 1 0
Register 45358
reserved
see 1
see 2
see 3
see 4
see 5
see 6
see 7
see 8
see 9
see 10
see 11
see 12
reserved