Schneider Electric 890USE17700 User Manual
Page 132

Data Exchange
132
890USE17700 April 2004
Fault Detection
The next eight contiguous registers (registers 45383 through 45390) indicate the
presence or absence of operational faults detected on the island bus modules. Each
bit represents a module:
z
A value of 1 in a bit indicates that the associated module is operating and that no
faults were detected.
z
A value of 0 in a bit indicates that the associated module is not operating either
because it has a fault or because it has not been configured.
The first two registers, shown below, provide the 32 bits that represent the module
locations available in a typical island configuration. The remaining six registers
(45385 through 45390) are available to support the island’s expansion capabilities:
15
14
13 12 11 10 9 8
7 6 5 4 3 2 1 0
Register 45383
module 1
module 2
module 3
module 4
module 5
module 6
module 7
module 16
module 8
module 9
module 10
module 11
module 12
module 13
module 14
module 15
15 14 13 12 11 10 9 8
7 6 5 4 3 2 1 0
Register 45384
module 17
module 18
module 19
module 20
module 21
module 22
module 23
module 32
module 24
module 25
module 26
module 27
module 28
module 29
module 30
module 31