Data Exchange

132

890USE17700 April 2004

Fault Detection

The next eight contiguous registers (registers 45383 through 45390) indicate the
presence or absence of operational faults detected on the island bus modules. Each
bit represents a module:

z

A value of 1 in a bit indicates that the associated module is operating and that no
faults were detected.

z

A value of 0 in a bit indicates that the associated module is not operating either
because it has a fault or because it has not been configured.

The first two registers, shown below, provide the 32 bits that represent the module
locations available in a typical island configuration. The remaining six registers
(45385 through 45390) are available to support the island’s expansion capabilities:

15

14

13 12 11 10 9 8

7 6 5 4 3 2 1 0

Register 45383

module 1

module 2

module 3

module 4

module 5

module 6

module 7

module 16

module 8

module 9

module 10

module 11

module 12

module 13

module 14

module 15

15 14 13 12 11 10 9 8

7 6 5 4 3 2 1 0

Register 45384

module 17

module 18

module 19

module 20

module 21

module 22

module 23

module 32

module 24

module 25

module 26

module 27

module 28

module 29

module 30

module 31