beautypg.com

Schneider Electric 890USE17700 User Manual

Page 25

background image

The STB NIP 2212 NIM

890USE17700 April 2004

25

The physical features of the STB NIP 2212 are described briefly in the following
table:

Feature

Function

1

Ethernet interface

An RJ-45 (See STB NIP 2212 Network Interface, p. 26)
connector is used to connect the NIM and the island bus to
an Ethernet LAN network.

2

MAC ID

48-bit, unique network ID hard-coded in the STB NIP 2212
when manufactured.

3

upper rotary switch

The rotary switches (See Physical Description, p. 28) used
together specify a role name for the STB NIP 2212.
Alternatively, the lower rotary switch can be used to direct the
STB NIP 2212 to use its MAC-based default IP address (See
Summary of Valid IP Address Settings, p. 29) or to obtain its
IP parameters from a BootP server or from the
STB NIP 2212 web site (See About the Embedded Web
Server, p. 67
).

4

lower rotary switch

5

space provided to record
IP address

Write the IP address that you assign to this STB NIP 2212
here.

6

power supply interface

A two-pin connector used to connect an external 24 VDC
power supply (See Selecting a Source Power Supply for the
Island’s Logic Power Bus, p. 39
) to the NIM.

7

LED array

Colored LEDs (See LED Indicators, p. 30) use various
patterns to visually indicate the operational status of the
island bus, activity on the NIM, and the status of
communications to the island over the Ethernet LAN.

8

removable memory card
drawer

A plastic drawer in which a removable memory card (See
Installing the STB XMP 4440 Optional Removable Memory
Card, p. 50
) can be seated and then inserted into the NIM.

9

CFG port cover

A hinged flap on the NIM’s front panel that covers the CFG
interface (See The CFG Interface, p. 33) and the RST button
(See The RST Button, p. 55).