6.4 Connecting the equipotential bonding circuit

SIMATIC Panel PC 877
Operating instructions, Release 07/2006, A5E00877780-01

6-7

6.4

6.4

Connecting the equipotential bonding circuit

A low resistance ground connection ensures that interference signals generated by external

power supply cables, signal cables or cables to the I/O modules are safely discharged to

ground.
The equipotential bonding connection of the device is located on the right-hand side of the

computer unit and is identified by the following symbol:

Figure 6-1

Equipotential bonding

Connecting the equipotential bonding circuit

You require a TORX T20 screwdriver to connect the equipotential bonding conductor.

Steps for connecting the equipotential bonding
(1) Connect the equipotential bonding connection (M4 thread)

(1) on the device (large surface, large-area contact) with the

central grounding point of the control cabinet.

The minimum permissible cross-section is 5 mm

2

.