beautypg.com

Siemens SIMATIC PANEL PC 877 User Manual

Page 172

background image

Technical data

15.1 General technical data

SIMATIC Panel PC 877

15-2

Operating instructions, Release 07/2006, A5E00877780-01

General technical data
Electromagnetic compatibility (EMC)
AC device: Emitted interference

EN 55011 Class A, EN 61000-3-2 Class D

EN 61000-3-3

DC device: Emitted interference

EN 55022 Class A

Noise immunity:

Mains borne disturbance variables on supply lines

± 2 kV; according to IEC 61000–4–4; Burst

± 1 kV; according to IEC 61000–4–5; Surge sym.

± 2 kV; according to IEC 61000–4–5; Surge asym.

Noise immunity on signal lines

± 1 kV;according to IEC 61000–4–4; Burst; length < 3 m

± 2 kV; according to IEC 61000–4–4; Burst; length > 3 m

± 2 kV; according to IEC 61000–4–5; surge; length > 30 m

Immunity to discharges of static electricity

± 6 kV contact discharge according to IEC 61000–4–2

± 8 kV air discharge according to IEC 61000–4–2

Immunity to RF interference

10 V/m 80–1000 MHz, 80% AM according to IEC 61000–4–3

10 V/m 900 MHz and 1.89 GHz, 50% ED according to IEC 61000–

4–3

10 V/m 9 KHz-80 MHz according to IEC 61000–4–6

Magnetic field

30 A/m, 50 Hz according to IEC 61000–4–8

Climatic conditions
Temperature

Operation

Installed in cabinet:

For external temperature of 40 °C

For external temperature of 45 °C

Storage, transportation

Gradient

Tested to IEC 60068–2–1, IEC 60068–2–2, IEC 60068–2–14

+ 5 °C up to + 45 °C

Internal temperature max. 50 °C

Internal temperature max. 45 °C

–20 °C to +60°C

max. 10° C/h in operation, 20° C/h storage, no condensation

Relative humidity

Operation

Storage/transport

Gradient

Tested to IEC 60068–2–78, IEC 60068–2–30

5% to 80 % at 25° C, no condensation

5% to 95% at 25° C, no condensation

Maximum 10° C/h, no condensation


Mechanical environmental conditions
Vibration

Operation

2)

Storage/transport

tested to DIN IEC 60068–2–6

10 to 58 Hz: 0.075 mm, 58 to 500 Hz: 9.8 m/s2 = 1g

5 to 9 Hz: 3.5 mm, 9 to 500 Hz: 9.8 m/s2 = 1g

Resistance to shock

Operation

2)

Storage/transport

Tested according to IEC 60068–2–27, IEC 60068–2–29

50 m/s

2

approx. 5 g, 30 ms

250 m/s

2

approx. 25 g, 6 ms