Siemens SIMATIC PANEL PC 877 User Manual
Page 47
Connecting
6.2 Connecting the 100 V to 240 V AC power supply
SIMATIC Panel PC 877
Operating instructions, Release 07/2006, A5E00877780-01
6-5
Power Factor Correction
The power supply contains an active PFC (Power Factor Correction) circuit to conform to the
EMC guidelines.
Uninterruptible AC power systems (UPS) must supply a sinusoidal output voltage in the
normal and buffered mode when used with SIMATIC PCs with an active PFC.
UPS characteristics are described and classified in the standards EN 50091-3 and IEC
62040-3. Devices with sinusoidal output voltage in the normal and buffered mode are
identified with the classification “VFI-SS-....” or “VI-SS-....”.
Notice
Risk of damage
Operation of the device on a non-sinusoidal mains voltage can cause damage to the power
supply unit.
Country-specific connection information
For the USA and Canada
A UL-listed power supply cable must be used in the United States and Canada.
Power cables are provided as an accessory for the specific country of delivery.
•
120 V supply voltage
Use a flexible power cable with UL approval and the following features: Type SJT with
three leads, min. 18 AWG conductor cross-section, max. 4.5 m long and parallel 15 A
ground contact connector, minimum rating 125 V.
•
230 V supply voltage
Use a flexible power cable with UL approval and the following features: Type SJT with
three leads, min. 18 AWG conductor cross-section, max. 4.5 m long and tandem 15 A
ground contact connector, minimum rating 250 V.
For countries other than the USA and Canada
•
Please note local supply voltages
This device is equipped with a safety-tested power cord which may only be connected to
a ground contact power outlet. If you choose not to use this cable, you must use a flexible
cable of the following type: Min 18 AWG conductor cross-section and 15 A / 250 V
shockproof connector. The cable set must be compliant with the safety regulations and
stipulated IDs of the country where the system is to be installed.
Connecting the power supply
Steps for connecting the device to the 100 / 240 V AC power supply
1 Switch off the AC power source
2 Connect the power supply using the connector
Power consumption
The maximum AC power consumption is 360 W.