Connecting

6.2 Connecting the 100 V to 240 V AC power supply

SIMATIC Panel PC 877
Operating instructions, Release 07/2006, A5E00877780-01

6-5

Power Factor Correction

The power supply contains an active PFC (Power Factor Correction) circuit to conform to the

EMC guidelines.
Uninterruptible AC power systems (UPS) must supply a sinusoidal output voltage in the

normal and buffered mode when used with SIMATIC PCs with an active PFC.
UPS characteristics are described and classified in the standards EN 50091-3 and IEC

62040-3. Devices with sinusoidal output voltage in the normal and buffered mode are

identified with the classification “VFI-SS-....” or “VI-SS-....”.

Notice
Risk of damage
Operation of the device on a non-sinusoidal mains voltage can cause damage to the power

supply unit.

Country-specific connection information

For the USA and Canada
A UL-listed power supply cable must be used in the United States and Canada.

Power cables are provided as an accessory for the specific country of delivery.

120 V supply voltage

Use a flexible power cable with UL approval and the following features: Type SJT with

three leads, min. 18 AWG conductor cross-section, max. 4.5 m long and parallel 15 A

ground contact connector, minimum rating 125 V.

230 V supply voltage

Use a flexible power cable with UL approval and the following features: Type SJT with

three leads, min. 18 AWG conductor cross-section, max. 4.5 m long and tandem 15 A

ground contact connector, minimum rating 250 V.

For countries other than the USA and Canada

Please note local supply voltages

This device is equipped with a safety-tested power cord which may only be connected to

a ground contact power outlet. If you choose not to use this cable, you must use a flexible

cable of the following type: Min 18 AWG conductor cross-section and 15 A / 250 V

shockproof connector. The cable set must be compliant with the safety regulations and

stipulated IDs of the country where the system is to be installed.

Connecting the power supply

Steps for connecting the device to the 100 / 240 V AC power supply
1 Switch off the AC power source
2 Connect the power supply using the connector

Power consumption

The maximum AC power consumption is 360 W.