–91–

Note 1 :

Symptoms of incorrect i.e, reverse connection of PS

1

and PS

3

to BC controller board

Note 2 :

Check using LED monitor display switch (outdoor MAIN board SW1)

Note 3 :

Check CNP1 (liquid measurement) and CMP3 (intermediate) connectors on BC controller board for disconnection or

looseness.

Note 4 :

With the sensor of the applicable connector removed from the board, use the LED monitor display switch (Note 1) to

check the pressure value.

Pressure Sensor Replacement Precaution

Symptom

Cooling-only

Cooling-principal

Heating-only

Heating-principal

Normal

Insufficient

cooling.

SC11 large

SC16 small

PHM < 0

SC11 large

SC16 small

PHM < 0

Warm indoor

SC small. When

SV opens some

noise produced.

SC11 small

SC16 small

PHM < 0

Insufficient heating

Warm indoor SC small

When SV opens some

noise produced.

Measured Data

High pressure of
outdoor

Low pressure satura-
tion temperature

Low pressure of
outdoor

BC controller pressure
(liquid measurement)

(intermediate)

Signal

HPS

TH2

LPS

PS1

PS3

SW1 Setting

Remarks

See converter.

See converter.

See converter.

Convert saturation
temperature to
desired pressure
using converter.

1

ON

2 3 4 5 6 7 8 9 10

1

ON

2 3 4 5 6 7 8 9 10

1

ON

2 3 4 5 6 7 8 9 10

1

ON

2 3 4 5 6 7 8 9 10

1

ON

2 3 4 5 6 7 8 9 10

(Pressure sensor output voltage)