–58–

Resistance check

Resistance check

Conductivity check
using tester.

Belt heater AC 200 to 240 V
MC1

1280

45 W

MC2 400: 1280

45 W

500: 1029

56 W

Code heater 2880

(1440

+ 1440

)

AC 220 to 240 V
20 W (10 W + 10 W)

AC 220 to 240 V
Not conducting: cooling cycle
Conducting

: heating cycle

Refrigerant heating inside compressor.

Refrigerant heating of accumulator
liquid level detection circuit.

Switching of cooling/heating cycle.

CH11
CH12
crankcase
heater

CH2
CH3
Accumulator
liquid level
detection

Heater

4-way
valve

Name

Code

(Function)

Inspection method

Application

Product code

Specification

Outdoor unit

Solenoid
vallve

Linear
expansion
valve

SV3~8 heat
exchanger
capacity
control

SV6a
discharge-
suction
bypass

SLEV (Oil re-
turn)

Controls heat exchanger capacity of
outdoor unit.

Evaporation of liquid refrigerant inside
MC2.

Adjusts the rate of refrigerant (oil) re-
turning from the accumulator.

AC 220 to 240 V
Close: conducting
Open : not conducting

AC 220 to 240 V
Open : conducting
Close: not conducting

DC 12 V stepping motor drive
valve opening amount 0 to
480 pulse (Direct drive type).

Same as indoor unit
LEV. However, the
resistance value is
different than the in-
door unit.

Conductivity test
using tester.

21S4a

21S4b