Checking code

Meaning, detecting method

Cause

Checking method & Countermeasure

Discharge
temperature
abnormality
(Outdoor unit)

1102

1. When 140˚C or more discharge

temperature is detected during
operations (the first time), out-
door unit stops once, mode is
changed to restart mode after
3 minutes, then the outdoor unit
restarts.

2. When 140˚C or more temp. is

detected again (the second
time) within 30 minutes after
stop of outdoor unit, emergency
stop is observed with code No.
“1102” displayed.

3. When 140˚C or more temp. is

detected 30 or more minutes
after stop of outdoor unit, the
stop is regarded as the first time
and the process shown in 1 is
observed.

4. 30 minutes after stop of outdoor

unit is intermittent fault check
period with LED displayed
(1202).

See Refrigerant amount check.

Check operating conditions and opera-
tion status of indoor/outdoor units.

Check operation status by actually
performing cooling or heating opera-
tions.

Cooling

: Indoor LEV

(Cooling-only) LEV1, 3 (BC)

SVM1 (BC)
SVA (BC)

Heating

: Indoor LEV

(Heating-only) LEV3 (BC)

SVB (BC)
SV3 ~ 8

See Trouble check of LEV and sole-
noid valve.

1) Gas leak, gas shortage.

2) Overload operations.

3) Poor operations of indoor LEV.
4) Poor operations of BC controller

LEV:
Cooling-only

: LEV3

Cooling-main : LEV1, 3
Heating-only, Heating-main:

LEV3

Defronst

: LEV3

5) Poor operations of BC controller

SVM1

:

Cooling-only, defrost

6) Poor operations of BC controller

SVA

:

Cooling-only, Cooling-main

7) Poor operations of BC controller

SVB

:

Heating-only, Heating-main

8) Poor operations of solenoid

valves.
SV (3 ~ 8)
Heating-only, Heating-main

9) Setting error of connection

address (PURY).

10)Poor operations of ball valve.

11) Outdoor unit fan block, motor

trouble, poor operations of fan
controller

Heating (Heating-only,

Heating-main).
3) ~ 11) : Rise in discharge
temp. by low pressure drawing.

12)Gas leak between low and high

pressures.
4-way valve trouble, compres-
sor trouble, solenoid valve
SV1 trouble.

13)Poor operations of solenoid valve

SV4a.
Bypass valve SV2 can not
control rise in discharge temp.

14)Thermistor trouble.

15)Thermistor input circuit trouble on

control circuit board.

Check address setting of indoor unit
connection.

Confirm that ball valve is fully opened.

Check outdoor fan.
See Trouble check of outdoor fan.

Check operation status of cooling-only
or heating-only.

See Trouble check of solenoid
valve.

Check resistance of thermistor.

Check inlet temperature of sensor
with LED monitor.