(3) Group registration of indoor unit

1)

Registration method

• Group registration of indoor unit ........................................................................

1

The indoor unit to be controlled by a remote controller is registered on the remote controller.

[Registration procedure]

1

With the remote controller under stopping or at the display of “HO”, continuously press the

FILTER

+

switch

(

A

+

B

) at the same time for 2 seconds to change to the registration mode. (See the figure below.)

2

Assign the indoor unit address to “INDOOR UNIT ADDRESS NO.” by operating the

(Room temperature

adjustment) (

C

).

Then press the

TEST RUN

switch (

D

) to register. In the figure below, the “INDOOR UNIT ADDRESS NO.” is being set

to 001.

3

After completing the registration, press the

FILTER

+

switch (

A

+

B

) at the same time for 2 seconds to

change to the original ordinary mode (with the remote controller under stopping).

• Remote controller under stopping

• “HO” under displaying

Ordinary mode

INDOOR UNIT

ADDRESS NO

ERROR CODE

OA UNIT ADDRESS NO

˚C

INDOOR UNIT

ADDRESS NO

ERROR CODE

OA UNIT ADDRESS NO

˚C

ERROR CODE

OA UNIT ADDRESS NO

˚C

1

1

Group setting mode

• Confirm the indoor unit address No.

• Confirm the connection of the transmission line.

ERROR CODE

OA UNIT ADDRESS NO

˚C

ERROR CODE

OA UNIT ADDRESS NO

˚C

• Registration complete

• Registration error

Indicates the type of unit
(Indoor unit in this case)

“88” flickers indicating registra-
tion error. (when the indoor unit
registered is not existing)

2

Assign the
address (

C

)

1

Change to the
registration
mode (

A

+

B

)

3

Press the
registration
switch (

D

)

Remote controller

System example

Indoor units

Group

2

+

3

ON/OFF

TEMP

FILTER

CHECK TEST

ON OFF

CLOCK

PAR-F27MEA

TIMER SET