Transmission processor hardware
error

Transmission circuit bus-busy er-
ror
1

Collision of data transmission:
Transmission can not be per-
formed for 4~10 consecutive
minutes due to collision of data
transmission.

2

Data can not be transmitted on
transmission line due to noise
for 4~10 consecutive minutes.

Note:

The address/attribute
shown on remote
controller indicates the
controller which has
detected error.

Checking method and processing

1) As the voltage of short frequency like

noise is mixed in transmission line
continuously, transmission processor
can not transmit.

2) Faulty controller of generating unit.

a) Check transmission wave shape/noise on trans-

mission line by following of transmission wave shape/noise>.

No noise indicates faulty controller of generat-
ing unit.

Noise if existed, check the noise.

Checking

code

6602

6603

Meaning, detecting method

Cause

Checking method & Countermeasure

Transmission line

installed while turning

power source on?

Check power source of indoor
unit.

220V ~ 240V?

Shut off the power source of outdoor/in-
door units/BC controller and make it again.

Erroneous power
source work

Erroneous transmis-
sion work

Check transmission line
work and shield finish

Ground fault or shield

contacted with transmission

line?

System composition?

Single refrigerant
system

Investigation of trans-
mission line noise

Modification of
faulty point

Replace insertion
of CN40 to CN41

CN40 inserted?

Confirm supply power
connector CN40 of outdoor unit

MELANS connected
system

Investigation of the
cause of noise

* For the investigation method, follow

tion method of transmission wave shape/noise>

Modification of CN40
insertion method.

Only 1 set with

CN40 inserted?

Noise exist?

Faulty controller of
generating unit

Plural refrigerant
system

Confirm supply power
connector CN40 of outdoor unit

NO

YES

YES

YES

NO

NO

YES

NO

YES

NO

YES