background image

–56–

1

Adjustment of super heat of heat
exchanger outlet port of indoor unit
during cooling.

2

Adjustment of sub-cool of heat ex-
changer outlet port of indoor unit

during heating.

Indoor unit control (Thermostat).

1

Indoor unit control (Freeze preven-
tion, hot adjust, etc.).

2

LEV control during heating (sub-cool
detection).

LEV control during cooling (super-heat
detection).

Uses the operating pressure to adjust
the operating frequency and adjust the
amount of circulating refrigerant.

When there is a load that cannot be
adjusted by MC1, this function ensures
the stable flow of refrigerant.

[4] List of Major Component Functions

Name

Code

(Function)

Electronic
expansion
valve

Thermistor

Compres-
sor

Outdoor unit

Inspection method

DC 12 V
Amount of opening of the
stepping motor drive valve
60 to 2000 pulse.
(Gear Type)

R

0

= 15 k

B

0/80

= 3460

Rt =
15exp{3460( - )}

0

°

C: 15 k

10

°

C: 9.7 k

20

°

C: 6.4 k

25

°

C: 5.3 k

30

°

C: 4.3 k

40

°

C: 3.1 k

Low-pressure shell scroll
type. Winding resitance
0.481 (20

°

C).

Low-pressure shell scroll type.
Winding resistance: each phase.
1.996 (20

°

C): P400 YMF-C

1.197 (20

°

C): P500 YMF-C

1

273+t

1

273

1

273+t

1

393

Application

Product code

Specification

Indoor unit

LEV

TH21
(Inlet air
temperature)

TH22
(Piping
temperature)

TH23
(Gas piping
temperature)

MC1

MC2

White

Red

Yellow Brown Blue

Orange

M

Perform a continuity
check using a tester.
Conductivity among
white, red and orange.
Conductivity among yel-
low, brown and blue.

Resistance value
check

Con-
nector

Pressure
0 to 30 kg/cm

2

G

(0 to 2.94 MPa)
Vout 0.5 to 3.5 V
Connector
GND (Black)
Vout (White)
Vc (DC 5 V) (Red)

1

273+t

1

273

63HS

Pressure
0 to 10 kg/cm

2

G

(0 to 0.98 MPa)
Vout 0.5 to 3.5 V
(0.3 V/kg/cm

2

, V/MPa)

Gnd (black)
Vout (white)
Vc (DC 5 V) (Red)

Con-
nector

63LS

Set to 30 kg/cm

2

G

(2.94 MPa) OFF.

R

120

= 7.465 k

B

25/120

= 4057

Rt =
7.465exp{4057( - )}

R

0

= 33 k

B

0/100

= 3965

R

t

=

33exp{3965( - )}

– 20

°

C: 92 k

– 10

°

C: 55 k

0

°

C: 33 k

10

°

C: 55 k

20

°

C: 13 k

30

°

C: 8.2 k

1

Detects high-pressure pressure.

2

Performs frequency control and high-
pressure protection.

1) Detects low-pressure.
2) Calculates the refrigerant circula-

tion configuration.

3) Protects the low pressure

1

Detects high-pressure.

2

Performs high-pressure protection.

1

Detects high-pressure pressure.

2

Performs high-pressure protection.

0

°

C: 698 k

60

°

C:

48 k

10

°

C: 413 k

70

°

C:

34 k

20

°

C: 250 k

80

°

C:

24 k

30

°

C: 160 k

90

°

C: 17.5 k

40

°

C: 104 k

100

°

C: 13.0 k

50

°

C: 70 k

110

°

C: 9.8 k

1

Detects low pressure saturation tem-
perature.

2

Performs frequency control and liq-
uid level of accumulator.

High
pressure
sensor

Low
pressure

sensor

Pressure

switch

Thermistor

63HS

63LS

63H1
62H2

TH11,12
(Outlet)

TH2 (Low
pressure
saturation
temperature)

Conductivity check

Resistance check

Resistance check