(12) Emergency response operating mode

The emergency operation mode is a mode in which the unit is run in an emergency to respond to the trouble when the

compressors (No. 1, No. 2) break down, making it possible to carry out a abnormality reset using the remote control.

1) Starting the Emergency Operation Mode

1

Trouble occurs (Display the abnormality code root and abnormality code on the remote control).

2

Carry out trouble reset with the remote control.

3

If the abnormality indicted in

1

above is of the kind that permits emergency operation (see the table below),

initiate a retry operation.

If the trouble indicated in

1

above is of the kind where emergency operation is impossible (see the table below),

restart operation after carrying out the previous abnormality reset (without entering the emergency operation

mode).

4

If the same abnormality is detected again during the retry operation in

3

above, carry out trouble reset once

more with the remote control, then try emergency operation starting corresponding to the contents of the

abnormality

Table Emergency Operation Mode Patterns and Abnormality Codes for which Emergency Operation is Possible or Impossible

Caution

During emergency operation, only X marked percentage of indoor units can be operated during emergency operation.

In case, more than X marked percentage of indoor units are operated, over than the percentage of indoor units

would be on the stand-by mode.

Codes for which emergency operation is
possible.

Emergency Mode
Pattern

Abnormality Codes for
which Emergency
Operation is Impossible

Action

When a No. 1
Compressor Failure
Occurs

When No. 2
Compressor Failure
Occurs

Trouble codes other than
those at left.

Emergency Operation only with the
No. 2 Compressor

* After the retry operation, even if

there is a different abnormality
code detected within Abnormality> at left, press the
button and after resetting, start
the unit by emergency operation.

[Example]

4250

Reset

Retry

4240

Reset

Emergency

operation

Emergency Operation only with the
No. 1 Compressor

Serial transmission abnormality

0403

VDC sensor/circuit abnormality

4200

Bus voltage abnormality

4220

Radiator panel overheat
protection

4230

Overcurrent protection

4240

IPM alarm output

4250

/Bus voltage abnormality
Thermal sensor abnormality
(Radiator panel)

5110

IAC sensor/circuit abnormality

5301

Overcurrent protection

400

500

No. 1 Compressor Failure

Ч

48 %

Ч

65 %

No. 2 Compressor Failure

Ч

65 %

Ч

65 %