Thermistor (Liquid and gas piping temperature detection)

Be careful when removing heavy parts.

Procedure

Photos

1. Remove the front panel

1

Use the procedure under (1)-1.2.3 to check

TH11, TH12, TH15, and TH16.

2. Disconnect the piping sensor lead from the control-

ler panel.

1

TH11 - TH12 (CN10)

2

TH15, TH16 (CN11)

3. Pull the temperature sensor from the temperature

sensor housing and replace it with a new sensor.

4. Connect the temperature sensor lead securely to

the controller board.

(4) Pressure Sensor

Procedure

Photos

1. Remove the front panel.

1

Use the procedure under (1)-1.2 to check PS1

and PS3.

2. Disconnect the connector of the applicable pressure

sensor from the controller board and insulate the

connector.

1

Liquid pressure sensor (CNP1)

2

Intermediate pressure sensor (CNP3)

3. Install a new pressure sensor at the location shown

in the photograph, and plug the connector into the

controller board.

Important

1

In the case of gas leakage from the pressure sen-

sor, take actions to fix the leak before performing

the above procedure.

PS1

PS3

TH16

TH11

TH15

TH12