Page 52

background image

–50–

YES

NO

YES

NO

YES

YES

NO

NO

Normal operations

Trouble observed

Stop

Start

Breaker

turned on

Set indoor ad-

dress No. to remote

controller

Operation
command

Operation

mode

Error mode

Cooling-only, Heating-only,
Cooling/heating mixed

Error stop

Operation

mode

Operation

mode

52C ON

[3] Operation Flow Chart

(1)

Outdoor unit

Note : 1

For about 3 minutes after turning on power source, address and group information of outdoor unit, BC, controller indoor unit,
and remote controller are retrieved by remote controller, during which “HO” blinks on and off on remote controller. In case
indoor unit is not grouped to remote controller, “HO” display on remote controller continues blinking even after 3 minutes after
turning on power source.

Note : 2

Two trouble modes included indoor unit side trouble, (BC controller trouble) and outdoor unit side trouble. In the case of indoor
unit side trouble, error stop is observed in outdoor unit only when all the indoor units are in trouble. However, if one or more
indoor units are operating normally, outdoor unit shows only LED display without undergoing stop.

Note : 3

Operation mode conforms to mode command by BC controller.

Note : 4

In case BC controller issues cooling/heating mixed operation mode, outdoor unit decides operation mode of cooling-main
operation or heating-main operation.

Note : 3

Note : 2

Note : 1

Fan

“HO” blinks on the remote

controller

Oil return LEV, fully closed

1. 52C

OFF

2. Inverter output

0Hz

3. Outdoor fan

Stop

4. All solenoid valve

OFF

Cooling (Cooling-

only) operations

Heating (Heating-

only) operations

Cooling-main

operations

Heating-main

operations

Operation mode command to (BC controller) outdoor unit

Error code blinks on the
outdoor controller board

Error command to

BC controller

Error code blinks on the

remote controller

Cooling/heating mixed

Note : 4