Note 1 Wait until the units stabilize as described in the refrigerant amount adjustment procedure in “Chapter

6

”.

Note 2 After the units are operating stably, check that the refrigerant composition of

α

OC is within the following

ranges, indicating that the composition check is finished.

If the accumulator liquid level AL = 0 when cooling:

α

OC = 0.20 ~ 0.26

If the accumulator liquid level AL = 1 when cooling:

α

OC = 0.23 ~ 0.34

When heating:

α

OC = 0.25 ~ 0.34

(The self-diagnosis switch (SW1) on the main board of the outdoor unit can be used to display this data on

the LED.)

[

α

OC self-diagnosis switch]

Note 3 TH2 and TH9:

Check and make any corrections using the same method as that for a faulty temperature

sensor, (refer to TROUBLESHOOTING).

LPS:

Check and make any corrections using the same method as that for a faulty low pressure

sensor, (refer to TROUBLESHOOTING).

CS circuit block: Set the self-diagnosis switch on the outdoor MAIN board as shown below.

Check and make any corrections so that “0” is displayed.

If any number other than 0 is displayed and TH2, TH9 or LPS are malfunctioning, correct them, then set

SW2-9 on the MAIN board of the outdoor unit from OFF to ON.

If any number other than 0 is displayed and TH2, TH9 or LPS are not malfunctioning, replace the CS

circuit if refrigerant is not flowing through it (while operating) and set SW2-9 on the MAIN board of the

outdoor unit from OFF to ON.

Note 4 If it can be verified that R407C was correctly charged in the liquid phase, continue to Yes. If there is a

possibility that it was not charged correctly, such as with a gas charger, continue to No.

Note 5 After reclaiming the system’s refrigerant, extract the air to create a vacuum, then refill with new refrigerant.

Be sure to charge in the liquid phase. In addition, be sure to change the dryer.

Note 6 After the units are operating stably, check that the refrigerant composition of

α

OC is within the following

ranges, indicating that the circulation check is finished.

If the accumulator liquid level AL = 0 when cooling:

α

OC = 0.21 ~ 0.25

If the accumulator liquid level AL = 1 when cooling:

α

OC = 0.24 ~ 0.28

When heating:

α

OC = 0.27 ~ 0.31

If the refrigerant composition of

α

OC is not within the ranges specified above, a large error has been

detected. Refer to section 1-3 in Chapter

6

, then after setting SW4-1 on the MAIN board of the outdoor unit

to ON, calibrate the refrigerant circulation constant

α

OC with SW4-2 until it is within the ranges specified

above.

After calibrating, keep the SW4-1 ON and finish the circulation check.

α

OC>

Conditions:

If the accumulator liquid level AL = 0 and

α

OC = 0.29 when cooling,

α

OC must be adjusted so

that it is between 0.21 and 0.25.

By switching SW4-2 between ON and OFF, adjustments can be made in the following order:

0

3%

6%

9%

12%

-6%

-3%

0

For this example, by making an adjustment of -0.06 (-6%),

α

OC can be adjusted to 0.23.

1. If SW4-2 is already set to OFF, change the switch 5 times.

OFF (0.29)

ON (0.32)

OFF (0.35)

ON (0.38)

OFF (0.41)

ON (0.23)

2. If SW4-2 is already set to ON, change the switch 5 times.

ON (0.29)

OFF (0.32)

ON (0.35)

OFF (0.38)

ON (0.41)

OFF (0.23)

1

ON

2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

ON